Delta VFD300C43S-HS User Manual page 27

Vector control drive (high speed models)
Table of Contents

Advertisement

2-2 Flow and Power Dissipation
Model No.
VFD300C43S-HS
VFD370C43S-HS
VFD750C43A-HS
VFD1100C43A-HS
VFD1600C43A-HS
VFD2200C43A-HS
VFD3550C43A-HS
The required airflow shown in chart is for installing single drive in a confined
space.
When installing multiple drives, the required air volume should be the
required air volume for single drive X the number of the drives
Air flow rate for cooling
Flow Rate [cfm]
External Internal
Total
148
32
180
148
32
180
188
32
220
327
80
407
316
199
515
619
619
1042
1042
3
Flow Rate [m
/hr]
External Internal Total
251
55
306
251
55
306
319
55
374
556
137
692
537
339
875
1051
1051
1770
1770
2-5
Chapter 2 InstallationC2000-HS
Power Dissipation
Power Dissipation [W]
Loss External
Internal
(Heat sink)
TBD
TBD
TBD
TBD
1408
334
2107
491
3096
687
The heat dissipation shown in
the chart is for installing single
drive in a confined space.
When installing the multiple
drives, volume of heat
dissipation should be the heat
dissipated for single drive X
the number of the drives.
Heat dissipation for each
model is calculated by rated
voltage, current and default
carrier.
Total
TBD
TBD
1742
2599
3783
5772
8007

Hide quick links:

Advertisement

Table of Contents
loading