2. PM Sensorless Adjustment (※ the number marked on the procedure corresponds the number
of following adjustment explanations)
I. PM Sensorless Adjustment Procedure
PM Sensorless FOC
Adjustment Procedure
1. AUE auto-tuning error
2. Measured resistance,
inductance or back
EMF error
Chapter 12 Description of Parameter SettingsC2000-HS
1.Parameter Reset
Pr.00-02=10
2.Pr.05-33 Motor type
=1(SPM) or 2(IPM)
3.Motor Parameter Setting
Pr01-01 額定頻率
Pr.01-01 Rated Frequency
Pr01-02 額定電壓
Pr.01-02 Rated Voltage
Pr.05-34 Full-load Current
Pr.05-35 Rated Power
Pr.05-36 Rated Rotor Speed
Pr.05-37 Motor Poles
4.Motor Parameter Auto-tuning
Pr.05-00=5
(PM dynamic auto-tuning)
or Pr.05-00=13
(PM static auto-tuning)
Press 'RUN'
Motor
auto-tuning
successful?
NO
YES
5. Set Control Mode
Pr.00-10=0 Speed mode
Pr.00-11=6 PM FOC control
6.Cycle the power
7. Initial Angle Detection
Pr.10-53 angle detection
0: Disable
1: Internal ¼ rated current
attracting the rotor to zero
degrees
2: High frequency injection (IPM)
3: Pulse injection (SPM)
8. No-load
Running
12.2-00-35
Check Motor Parameters
Pr.05-38 PM system inertia
Pr.05-39 Rs stator resistance
Pr.05-40 Permanent magnet
motor Ld
Pr.05-41 Permanent magnet
motor Lq
Pr.05-43 Ke parameter
PMFOC mode set "6".
For IPM motor, set"2".
For SPM motor, set "3"
When both "2, 3" do not
perform well, then set "1"