Terminal Counting Value Reached (returns to 0)
Settings 0–65500
You can set the input point for the counter using the multi-function terminal MI6 as a trigger
terminal (set Pr. 02-06 to 23). When counting is completed, the specified multi-function output
terminal is activated (Pr.02-13, Pr. 02-14, Pr. 02-36, Pr. 02-37 are set to 18). Pr. 02-19 cannot be
set to 0 at this time.
Example: When the displayed value is c5555, the drive count is 5,555 times. If the displayed
value is c5555, the actual count value is 55,550–55,559.
Preliminary Counting Value Reached (does not return to 0)
Settings
When the count value counts from 1 to reach this value, the corresponding multi-function output
terminal is activated (Pr. 02-13, Pr. 02-14, Pr. 02-36, Pr. 02-37 are set to 17). You can use this
parameter as the end of counting to make the drive run from the low speed to stop.
Digital Output Gain(DFM)
Settings
Sets the signal for the digital output terminals (DFM-DCM) and the digital frequency output (pulse,
work period = 50 %). The output pulse per second = output frequency Pr.02-21.
Desired Frequency Reached 1
Settings
The upper limit of setting range is the same as the maximum operating frequency for Pr. 01-00.
The Width of the Desired Frequency Reached 1
Settings
Desired Frequency Reached 2
Settings
The upper limit of setting range is the same as the maximum operating frequency for Pr. 01-00.
0–65500
1–166
0.0–1500.0 Hz
0.0–1500.0 Hz
0.0–1500.0 Hz
12.1-02-21
Chapter 12 Description of Parameter SettingsC2000-HS
Default: 0
Default: 0
Default: 1
Default: 600.0
Default: 2.00
Default: 600.0