Delta VFD300C43S-HS User Manual page 446

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
If entering the low magnetic area and the input voltage (or DC BUS) plummets (e.g. an unstable
power net causes instant insufficient voltage, or a sudden load that makes DC BUS drop), which
causes the ACR diverge and oc, then increase the gain. If the Id value of a spur creates large
noise in high-frequency output current, decrease the gain to reduce the noise. Decrease the gain
will slow down the response.
PM Sensorless Control Word
Settings
bit No.
2
Choose a control mode to start.
3
Choose a mode to stop.
5
Choose a control mode to stop
Frequency Point to Switch from I/F Mode to PM Sensorless Mode
Settings
The upper limit is the same as the maximum operation frequency for Pr.01-00.
Sets the frequency for the switch point from low frequency to high frequency.
If the switch point is too low, the motor does not generate enough back-EMF to let the speed
estimator measure the rotor right position and speed, and causes stall and oc when running at
the switch point frequency
If the switch point is too high, the active area of I/F is too wide, which generates more current and
cannot save energy. If the current value for Pr.10-31 is too high, the high switch point makes the
drive continue to output with the setting value for Pr.10-31.
Frequency Point to Switch from PM Sensorless Mode to I/F Mode
Settings
The upper limit is the same as the maximum operation frequency for Pr.01-00.
Sets the switch point from high frequency to low frequency.
If the switch point is too low, the motor does not generate enough back-EMF to let the speed
estimator measure the rotor right position and speed when running at the switch point frequency.
If the switch point is too high, the active area of I/F is too wide, which generates more current and
cannot save energy. If the current of Pr. 10-31 is too high, the high switch point makes the drive
continue to output with the setting value for Pr. 10-31).
0000–FFFFh
Function
0.0–1500.0 Hz
0.0–1500.0 Hz
Description
0: Start in IF mode
1: Start in VF mode
0: Stop in IF mode
1: Stop in VF mode
0: When lower than Pr. 10-40, coast to stop
1: When lower than Pr. 10-40, ramp to stop
12.1-10-9
Default: 0000h
Default: 20.0
Default: 20.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents