Chapter 16 PLC Function ApplicationsC2000-HS
API
ZRST
40
Bit device
X
Y
M
D1
*
*
D2
*
*
Notes on operand usage:
Number of operand D
Operands D
, D
must designate the same type of device
1
2
Please refer to the function specifications table for each device in
series for the scope of device usage
When X0 is On, auxiliary relays M300–M399 will be cleared and changed to Off.
When X1 is On, 16-bit counters C0–C127 will all be cleared. (Writes 0, and clears
and changes contact and coil to Off).
When X10 is On, timer T0–T127 will all be cleared. (Writes 0, and clears and
changes contact and coil to Off).
When X3 is On, the data in data registers D0–D100 will be cleared and set as 0.
Devices can independently use the clear command (RST), such as bit device Y, M
and word device T, C, D.
D1
D2
P
Word device
K
H
KnX KnY KnM
operand ≤ number of operand D
1
D
: Clear range's initial device. D
1
When the number of operand D
designated by D
will be cleared.
2
X0
X1
X10
X3
X0
Clear range
16-bit command (5 STEP)
T
C
D
ZRST
execution type
*
*
*
*
*
*
32-bit command
2
Flag signal: none
: Clear range's final device.
2
> number of operand D
1
ZRST
M300
ZRST
C0
ZRST
T0
ZRST
D0
RST
RST
RST
16-72
Continuous
ZRSTP
execution type
, only the operand
2
M399
C127
T127
D100
M0
T0
Y0
Pulse