Chapter 12 Description of Parameter SettingsC2000-HS
PTC Level / KTY84 Level
Settings
 When Pr. 06-86 = 0, the setting range is 0.0–100.0, with unit %, and the default is 50.0%.
When Pr. 06-86 = 1, the setting range is 0.0–150.0, with unit ºC, and the default is 125.0ºC
 Sets AVI/ACI/AUI analog input function Pr. 03-00–03-02 to 6 [Positive Temperature Coefficient
(P.T.C.) thermistor input value)].
 The AUI terminal does not support KTY84-130.
 Use this to set the PTC / KTY84 level, the corresponding value for 100% is the analog input
maximum value.
 When Pr. 06-86 is set as KTY84, Pr. 06-30 setting range and the unit changes automatically.
Frequency Command for Malfunction
Settings
 When a malfunction occurs, check the current frequency command. If it happens again, it
overwrites the previous record.
Output Frequency at Malfunction
Settings
 When a malfunction occurs, check the current output frequency. If it happens again, it overwrites
the previous record.
Output Voltage at Malfunction
Settings
 When a malfunction occurs, check the current output voltage. If it happens again, it overwrites the
previous record.
DC Voltage at Malfunction
Settings
 When a malfunction occurs, check the current DC voltage. If it happens again, it overwrites the
previous record.
Output Current at Malfunction
Settings
 When a malfunction occurs, check the current output current. If it happens again, it overwrites the
previous record.
0.0–100.0 %
0.0–1500.0 Hz
0.0–1500.0 Hz
0.0–6553.5 V
0.0–6553.5 V
0.0–6553.5 Amp
12.1-06-14
Default: 50.0
Default: Read only
Default: Read only
Default: Read only
Default: Read only
Default: Read only