Chapter 13 Warning CodesC2000-HS
ID No.
Display on LCM Keypad
41
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
Incorrect setting of CANopen
station address
ID No.
Display on LCM Keypad
42
Action level
Action time
Warning setting parameter
Reset method
Reset condition
Record
Cause
CANopen internal memory error
Warning Name
CANopen station
CANopen station address error (only supports 1–127)
address error (CAdn)
Action and Reset
CANopen station address error
Immediately act when the fault is detected
N/A
Manual Reset
Pr. 00-02=7
When Pr. 00-21≠3, CAdn is a "Warning", and the warning is not recorded
1. Disable CANopen (Pr. 09-36=0)
2. Reset CANopen (Pr. 00-02=7)
3. Reset CANopen station address (Pr. 09-36)
Warning Name
CANopen memory
CANopen memory error
error (CFrn)
Action and Reset
When the user update firmware version of the control board, the FRAM internal
data will not be changed, then CFrn fault will occur.
Immediately act when the fault is detected
N/A
Manual Reset
Pr. 00-02=7
When Pr. 00-21≠3, CFrn is a "Warning", and the warning is not recorded
1. Disable CANopen (Pr. 09-36=0)
2. Reset CANopen (Pr. 00-20=7)
3. Reset CANopen station address (Pr. 09-36)