Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
Example 02: PID positive feedback
Pr. 08-10 must < Pr. 08-11
30kg is the reference
Set the parameter:
Pr. 03-00 = 5 (AVI is PID feedback)
Pr. 08-00 = 4 (PID positive feedback: AVI
simulation input function select)
Pr. 08-10 = 110% (Sleep reference:
Pr. 08-11 = 120% (Wake-up reference:
Case 01: If feedback <33kg, frequency decreases.
Case 02: If feedback >36kg, frequency increases.
PID Output Command Limit (Reverse Limit)
Settings
When reverse PID is allowed, and the PID output value is negative, the PID output value is
limited at the setting value for Pr.08-26. This parameter needs to be used with Pr.08-21.
Acceleration / Deceleration Time for PID Command
Settings
33kg = 110%*30kg)
36kg = 120%*30kg)
0.0–100.0%
0.00–655.35 sec.
12.1-08-12
Area
Physical quantity
>36kg, the drive goes
Sleep area
into sleepmotor goes
into sleep
between 33kg and
Excessive
36kg, the drive remains
area
in the current state
Wake-up
<33kg, the drive
area
wakes-up
Default: 100.0
Default: 0.00
PID