Delta VFD300C43S-HS User Manual page 789

Vector control drive (high speed models)
Table of Contents

Advertisement

Torque control:
Register table for torque mode:
Control special M
Special M
M1040
Servo On
Status special M
Special M
M1056
Servo On Ready
M1063
Torque attained
Control special D
Special D
D1060
Operating mode setting (torque mode is 2)
Status special D
Special D
D1050
Actual operating mode (speed mode is 0)
D1053
Actual torque
Torque mode control commands:
TORQ(P)
Target torque (with numbers)
Example of torque mode control:
The setting of electromechanical parameters involved in torque control must be completed before
implementing torque control.
1.
Set D1060 = 2 to change the converted to the torque mode.
2.
Use the TORQ command to implement torque control and speed limits.
3.
Set M1040 = 1; the drive will now be excited, and immediately jump to the target torque or
speed limit. D1053 can be used to find out the current torque.
0
M1002
ON only for 1scan a
M1000
6
Normally open contact
13
X1
Set Torque
X1
19
Set Torque
M0
25
Ready
28
9999
Description of Function
Description of Function
Description of Function
Description of Function
S1
T0
Power on delay
X4
16-147
Chapter 16 PLC Function ApplicationsC2000-HS
S2
Frequency restrictions
MOV
K2
D1060
Set control mode (0:V)
K30
TMR
T0
Power on delay
Ready
K1000
TORQ K100
TORQ K-200 K1000
Power on
END
Attributes
RW
Attributes
RO
RO
Attributes
RW
Attributes
RO
RO

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents