Chapter 12 Description of Parameter SettingsC2000-HS
Settings
Functions
23
Input the counter value
24
FWD JOG command
25
REV JOG command
TQC / FOC mode
26
selection
27
ASR1 / ASR2 selection
28
Emergency stop (EF1)
ON: the counter value increases by 1. Use the function with Pr.
02-19.
This function is valid when the source of the operation
command is external terminal. ON: the drive executes forward
JOG. When executing the JOG command in torque mode, the
drive automatically switches to speed mode. The drive returns
to torque mode after the JOG command is complete.
This function is valid when the source of the operation
command is external terminal. ON: the drive executes reverse
JOG. When executing the JOG command in torque mode, the
drive automatically switches to speed mode. The drive returns
to torque mode after the JOG command is complete.
ON: TQC mode.
OFF: FOC mode.
ON: the speed is adjusted by the ASR 2 setting. OFF: the speed
is adjusted by the ASR 1 setting. Refer to Pr. 11-02 for details.
ON: the output of the drive stops immediately, displays "EF1" on
the keypad, and the motor is in free run status. The drive keeps
running until the fault is cleared after you press RESET on the
keypad (EF: External Fault).
12.1-02-6