Delta VFD300C43S-HS User Manual page 414

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsC2000-HS
Wake-up Frequency
Settings
 The upper limit is the same as the maximum operation frequency for Pr. 01-00.
 When Pr. 08-18 = 0, the unit for Pr. 08-10 and that for Pr. 08-11 switch to frequency. The settings
are become 0.0–1500.0 Hz.
 When Pr. 08-18=1, the unit for Pr. 08-10 and that for Pr. 08-11 switch to percentage. The
settings then are to 0–200.00%.
 The percentage is based on the current command value, not the maximum value. For example,
if the maximum value is 100 kg, and the current value is 30kg, then if Pr. 08-11 = 40%, the value
is 12 kg.
 Pr.08-10 uses the same logic for calculation.
Sleep Time
Settings
 When the frequency command is smaller than the sleep frequency and less than the sleep time,
the frequency command is equal to the sleep frequency. However, the frequency command
remains at 0.00 Hz until the frequency command becomes equal to or larger than the wake-up
frequency.
PID Deviation Level
Settings
PID Deviation Time
Settings
 When the PID control function is normal, it should calculate the value within a period of time that
is close to the target value.
 Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr. 08-13 PID Deviation Level and exceeds Pr. 08-14
setting, it is judged as a PID control fault, and the multi-function output MOx = 15 (PID feedback
error) activates.
PID Feedback Filter Time
Settings
PID Compensation Selection
Settings
 0: The setting for Pr.08-17 gives the PID compensation value.
0.0–1500.0 Hz
0.0–6000.0 sec.
1.0–50.0%
0.1–300.0 sec.
0.1–300.0 sec.
0: Parameter setting (Pr. 08-17)
1: Analog input
12.1-08-8
Default: 0.0
Default: 0.0
Default: 10.0
Default: 5.0
Default: 5.0
Default: 0