65: PG Card Error (PGF5)
68: Sensorless estimated speed have wrong
direction
69: Sensorless estimated speed is over speed
70: Sensorless estimated speed deviated
72: Channel 1 (STO1–SCM1) safety loop error
(STL1)
73: External safety gate S1
75: external brake error
76: Safe Torque Off (STO)
77: Channel 2 (STO2–SCM2) safety loop error
(STL2)
78: Internal loop error (STL3)
82: U phase output phase loss (OPHL)
83: V phase output phase loss (OPHL)
84: W phase output phase loss (OPHL)
85: PG-02U ABZ hardware disconnection
86: PG-02U UVW hardware disconnection
89: Initial rotor position detection error
90: Inner PLC function is forced to stop
101: CANopen software disconnect 1 (CGdE)
102: CANopen software disconnect 2 (CHbE)
104: CANopen hardware disconnect (CbFE)
105: CANopen index setting error (CldE)
106: CANopen slave station number setting error
(CAdE)
107: CANopen index setting exceed limit (CFrE)
111: Internal communication overtime error (ictE)
112: PM sensorless shaft Lock error
PTC Detection Selection / PT100 Motion
Settings
Sets the operation mode of a drive after you set Pr. 06-29 to define PTC / PT100 / KTY84
detection.
Fault Code
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
Chapter 12 Description of Parameter SettingsC2000-HS
bit0
bit1
current Volt.
12.1-06-13
bit2
bit3
bit4
bit5
OL
SYS
FBK
EXI
Default: 0
bit6
CE