Over-torque Detection Selection (OT1)
Settings
Over-torque Detection Selection (OT2)
Settings
 When you set Pr. 06-06 and Pr. 06-09 to 1 or 3, a warning message displays, but there is no error
record.
 When you set Pr. 06-06 and Pr. 06-09 to 2 or 4, a warning message displays and there is an error
record.
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT2)
Settings
Over-torque Detection Time (OT2)
Settings
 When the output current exceeds the over-torque detection level (Pr. 06-07 or Pr. 06-10) and
exceeds the over-torque detection time (Pr. 06-08 or Pr. 06-11), the over-torque detection follows
the setting of Pr. 06-06 and Pr. 06-09.
When you set Pr. 06-06 or Pr. 06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running. The warning remains on until the output current is smaller than 5% of the over-torque
detection level.
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
10–250% (100% corresponds to the rated current of the drive)
0.0–60.0 sec.
10–250% (100% corresponds to the rated current of the drive)
0.0–60.0 sec.
12.1-06-5
Chapter 12 Description of Parameter SettingsC2000-HS
Default: 0
Default: 0
Default: 120
Default: 0.1
Default: 120
Default: 0.1