Delta VFD300C43S-HS User Manual page 250

Vector control drive (high speed models)
Table of Contents

Advertisement

Chapter 11 Summary of Parameter SettingsC2000-HS
Pr.
Parameter Name
Emergency stop (EF) & force to
07-20
stop selection
Automatic energy-saving
07-21
selection
07-22
Energy-saving gain
Auto voltage regulation (AVR)
07-23
function
Torque command filter time
07-24
(V/F and SVC control mode)
Slip compensation filter time
07-25
(V/F and SVC control mode)
Torque compensation gain (V/F
07-26
and SVC control mode)
Slip compensation gain (V/F and
07-27
SVC control mode)
07-29
Slip deviation level
Over slip deviation detection
07-30
time
07-31
Over slip deviation treatment
Motor shock compensation
07-32
factor
07-33
Auto-restart interval of fault
PMSVC voltage feedback
07-38
forward gain
07-62
dEb gain (Kp)
07-63
dEb gain (Ki)
Setting Range
when AC motor drive stops.
3: Fan turns ON when temperature (IGBT) reaches
around 60°C.
4: Fan always OFF
0: Coast to stop
st
1: Stop by the 1
deceleration time
2: Stop by the 2
nd
deceleration time
3: Stop by the 3
rd
deceleration time
th
4: Stop by the 4
deceleration time
5: System deceleration
6: Automatic deceleration
0: Disable
1: Enable
10–1000%
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0.001–10.000 sec.
0.001–10.000 sec.
IM: 0–10 (when Pr. 05-33 = 0)
PM: 0–5000 (when Pr. 05-33 = 1 or 2)
0.00–10.00
0.0–100.0%
0: No detection
0.0–10.0 sec.
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0–10000
0: Disable
0.0–6000.0 sec.
0.50–2.00
0–65535
0–65535
11-34
Default
0
0
100
0
0.500
0.100
0
0.00
(Default is
1.00 in SVC
mode)
0
1.0
0
1000
60.0
1.00
8000
150