Accumulated Motor Operation Time (Min)
Settings
Accumulated Motor Operation Time (Day)
Settings
Use Pr. 05-31 and Pr. 05-32 to record the motor operation time. To clear the operation time, set Pr.
05-31 and Pr. 05-32 as 00. An operation time shorter than 60 seconds is not recorded.
Induction Motor (IM) or Permanent Magnet Synchronous Motor Selection
Settings
Full-load current for a Permanent Magnet Motor
Settings
Sets the full-load current for the motor according to motor's nameplate. The default is 90% of the
drive's rated current.
For example: The rated current of a 7.5 HP (5.5 kW) is 25 A. The default is 22.5A.
The setting range is between 40%
25*40 %=10 A and 25*120 %=30 A
Rated Power for a Permanent Magnet Motor
Settings
Sets the rated power for the permanent magnet synchronous motor. The default is the drive's
power value.
Rated speed for a Permanent Magnet Motor
Settings
Pole number for a Permanent Magnet Motor
Settings
System Inertia for a Permanent Magnet Motor
Settings
Default values are as below:
–
0
1439
–
0
65535
0: IM (Induction Motor)
1: SPM (Surface permanent magnet motor)
2: IPM (Interior permanent magnet motor)
Depending on the model power
–
120% of rated current.
–
0.00
655.35 kW
–
0
65535 rpm
–
0
65535
–
0.0
6553.5 kg-cm
2
12.1-05-6
Chapter 12 Description of Parameter SettingsC2000-HS
Default: 0
Default: 0
Default: 0
Default: Depending
on the model power
Default: Depending on
the model power
Default: 2000
Default: 10
Default: Depending
on the motor power