3.3 Basic Operator Panel 20 (BOP20)

Settings in STARTER for direct online connection via PROFIBUS
The following settings are required in STARTER for communication via PROFIBUS:
● Extras -> Set PG/PC interface
Add/remove interfaces
● Extras -> Set PG/PC interface... -> Properties
Note
• Baud rate
• PROFIBUS addresses
3.3
Basic Operator Panel 20 (BOP20)
Brief description
The Basic Operator Panel 20 (BOP20) is a basic operator panel with six keys and a display
unit with background lighting. The BOP20 can be plugged onto the SINAMICS Control Unit
and operated.
The following functions are possible using BOP20
● Entering parameters
● Display of operating modes, parameters, alarms and faults
● Powering-up/powering-down while commissioning
Further information: See 'Parameterizing using the BOP20 (Basic Operator Panel 20)'
chapter
52
Activate/deactivate "PG/PC is the only master on the bus".
Switching STARTER to a working PROFIBUS:
STARTER automatically detects the baud rate used by SINAMICS for the PROFIBUS.
Switching the STARTER for commissioning:
The Control Unit automatically detects the baud rate set in STARTER.
The PROFIBUS addresses for the individual drive units must be specified in the
project and must match the address settings on the devices.
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
Drive functions