Parameterization with STARTER
The "Speed setpoint" parameter screen is selected with the
STARTER commissioning tool:
7.3.7.8

Suppression bandwidths and setpoint limits

Description
In the range 0 U/min to setpoint speed, a drive train (e.g. motor, coupling, shaft, machine)
can have one or more points of resonance, which can result in vibrations. The suppression
bandwidths can be used to prevent operation in the resonance frequency range.
The limit speeds can be set via p1080[D] and p1082[D]. These limits can also be changed
during operation with the connectors p1085[C] and p1088[C].
Figure 7-60
Function diagrams (see SINAMICS S110 List Manual)
● 1550 Setpoint channel
● 3050 Suppression bandwidth and speed limiting
264
Suppression bandwidths, setpoint limitation
icon in the toolbar of the
Function Manual, 10/2008, 6SL3097-4AB10-0BP0