Safety Integrated Functions
8.9 Acceptance test and acceptance report
No.
4.
Select STO/SS1 during the traversing command.
Note:
The acceptance test must be conducted for each configured control individually, either via terminals or PROFIsafe.
5.
Check the following:
Drive is braked and stopped by the mechanical brake.
No safety faults or alarms (r0945, r2122)
r9772.0 = r9772.1 = 1 (STO selected and active – CU)
r9872.0 = r9872.1 = 1 (STO selected and active – MM)
r9773.0 = r9773.1 = 1 (STO selected and active – drive)
r9772.4 = r9872.4 = 1 (SBC requested – CU and MM)
6.
Deselect STO
7.
Check the following:
Vertical axis:
Mechanical brake remains applied
No vertical axis:
Mechanical brake is released
No safety faults or alarms (r0945, r2122)
r9772.0 = r9772.1 = 0 (STO deselected and inactive – CU)
r9872.0 = r9872.1 = 0 (STO deselected and inactive – MM)
r9773.0 = r9773.1 = 0 (STO deselected and inactive – drive)
r9772.4 = r9872.4 = 0 (SBC not requested – CU and MM)
r0046.0 = 1 (drive in "Switching on inhibited" state)
8.
Acknowledge "Switching on inhibited" and run the drive
(vertical axis: mechanical brake is released)
9.
Ensure that the correct drive is running
The following is tested:
The brake is connected properly
The hardware is functioning properly
The SBC is parameterized correctly
Routine for the forced dormant error detection of the brake control
372
Description
Function Manual, 10/2008, 6SL3097-4AB10-0BP0