A07015 drive: Motor temperature sensor alarm
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
When the fault occurs, the time is started in p0607. If the fault is still present after this time
has expired, then fault F07016 is output; however, at the earliest, 1 s after alarm A07015.
If an SME Module is used (p0601 = 10), parameter r2124 displays the number of the sensor
channel that has triggered the message.
F07016 drive: Motor temperature sensor fault
An error was detected when evaluating the temperature sensor set in p0600 and p0601.
If alarm A07015 is present, the time in p0607 is started. If the fault is still present after this
time has expired, then fault F07016 is output; however, at the earliest, 1 s after alarm
A07015.
If an SME Module is used (p0601 = 10), parameter r0949 displays the number of the sensor
channel that has triggered the message.
Function diagrams (see SINAMICS S110 List Manual)
● 8016 Signals and monitoring - Thermal monitoring of motor
Overview of important parameters (see SINAMICS S110 List Manual)
● r0035 Motor temperature
● p0600[0..n] Motor temperature sensor for monitoring
● p0601[0..n] Motor temperature sensor type
● p0604[0...n] Motor overtemperature alarm threshold
● p0605[0...n] Motor overtemperature fault threshold
● p0606[0...n] Motor overtemperature timer stage
● p0607[0...n] Temperature sensor fault timer stage
● p0610[0...n] Motor overtemperature reaction
● p460x[0...n] Motor temperature sensor (x+1) sensor type, x = 0..3
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
General information for commissioning
1.4 Temperature sensors for SINAMICS components