Communication PROFIBUS DP
9.1 Communication according to PROFIdrive
Bit
Meaning
5
Restart ramp-function generator
Note:
The ramp-function generator cannot be frozen via p1141 in jog mode (r0046.31 = 1).
6
Enable speed setpoint
7
Acknowledge fault
Note:
Faults are acknowledged at a 0/1 edge via BI: p2103.
8..9
Reserved
10
Master control by PLC
Note:
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1".
11
Setpoint inversion
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
12
Reserved
13
Motorized potentiometer, setpoint, raise
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
14
Motorized potentiometer, setpoint, lower
(Only with "extended setpoint channel"
and "extended ramp-function
generator")
15
Reserved
394
Remarks
0
Inhibit ramp-function generator
Set ramp-function generator output to zero
1
Restart ramp-function generator
0
Freeze ramp-function generator
1
Enable setpoint
0
Inhibit setpoint
Set ramp-function generator input to zero
0/1
Acknowledge fault
0
No effect
-
-
1
Master control by PLC
This signal must be set so that the process data
transferred via PROFIdrive are accepted and
become effective.
0
PLC has no master control
Process data transferred via PROFIdrive are
rejected - i.e. assumed to be zero.
1
Setpoint inversion
0
No setpoint inversion
-
-
1
Motorized potentiometer, setpoint, raise
0
Motorized potentiometer setpoint raise not
selected
1
Motorized potentiometer, setpoint, lower
0
Motorized potentiometer setpoint lower not
selected
-
-
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
BICO
BI: p1141
BI: p1142
BI: p2103
-
BI: p0854
BI: p1113
-
BI: p1035
BI: p1036
-
Drive functions