Siemens Sinamics S110 Function Manual page 453

Hide thumbs Also See for Sinamics S110:
Table of Contents

Advertisement

● PROFIBUS interface
● PROFIBUS diagnostic LED
Setting the PROFIBUS address
Two methods are available for setting the PROFIBUS address:
1. Via the PROFIBUS address switches on the Control Unit
2. Via p0918
Example:
Setting the PROFIBUS address using the PROFIBUS address switches on the Control Unit.
Figure 9-19
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
The PROFIBUS interface is described in the following documentation:
References: SINAMICS S110 Equipment Manual
Note
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics purposes.
– In this case, p0918 is read-only and simply displays the set address.
– A change is not effective until POWER ON.
– You can only use this method when all the PROFIBUS address switches from S1 to
S7 are set to ON or OFF.
– Address changes made via parameters must be saved in a non-volatile memory using
the "Copy from RAM to ROM" function.
– A change is not effective until POWER ON.
Example: PROFIBUS address via PROFIBUS address switch on Control Unit
Communication PROFIBUS DP
9.2 Communication via PROFIBUS DP
453

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents