E_DIGITAL
MT_ZSW
MTn_ZS_F/MTn_ZS_S
CU_ZSW1
These process data are part of the central process data.
MELDW (message word)
See function diagram [2456]
Table 9- 18
Description of MELDW (message word)
Bit
Meaning
0
Ramp-up/ramp-down completed /
ramp-function generator active
1
Torque utilization < p2194
Application:
This message indicates that the motor is overloaded and appropriate measures need to be taken to rectify the
situation (e.g. stop the motor or reduce the load).
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
Remarks
1
Ramp-up/ramp-down completed.
The ramp-up procedure is completed once the
speed setpoint has been changed.
1/0
Ramp-up starts.
The start of the ramp-up procedure is detected as
follows:
The speed setpoint changes,
and
The defined tolerance bandwidth (p2164) is
exited.
0
Ramp-function generator active
The ramp-up procedure is still active once the
speed setpoint has been changed.
0/1
Ramp-up ends.
The end of the ramp-up procedure is detected as
follows:
The speed setpoint is constant,
and
The actual speed value is within the tolerance
bandwidth and has reached the speed setpoint,
and
The delay time (p2166) has elapsed.
1
Torque utilization < p2194
The current torque utilization is less than the set
torque utilization threshold (p2194),
or
Ramp-up is not yet complete.
0
Torque utilization > p2194
The current torque utilization is greater than the
set torque utilization threshold (p2194).
Communication PROFIBUS DP
9.1 Communication according to PROFIdrive
BICO
BO: r2199.5
BO: r2199.11
411