Diagnostics
5.2 Diagnostics via STARTER
Signal chart for measuring sockets
Figure 5-11
Which signal can be output via measuring sockets?
The signal to be output via a measuring socket is specified by parameterizing the connector
input p0771[0...1].
Important measuring signals (examples):
r0060
r0063
r0069[0...2]
r0075
r0076
r0077
r0078
Scaling
Scaling specifies how the measuring signal is processed. A straight line with 2 points must
be defined for this purpose.
Example:
x1 / y1 = 0.0% / 2.49 V x2 / y2 = 100.0% / 4.98 V (default setting)
– 0.0% is mapped onto 2.49 V
– 100.0% is mapped onto 0.00 V
100
Signal chart for measuring sockets
CO: Speed setpoint before speed setpoint filter
CO: Actual speed value
CO: Phase currents actual value
CO: Field-generating current setpoint
CO: Field-generating actual current
CO: Torque-generating current setpoint
CO: Torque-generating actual current
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
Drive functions