Commissioning with PROFIBUS
3.2 STARTER commissioning tool
Restoring the factory settings
You can use this function (p0970 = 1) to set all the parameters in the work memory of the
Control Unit to the factory settings. The CU305 will then perform an automatic start. All
relevant parameters found are written to the work memory (RAM). As part of this process,
various factory-set parameters are automatically updated to actual (more recent) values.
Once this automatic configuration is complete, a project with all available drive parameters
will be available in the target system.
This function, which is called "Restore factory settings", can be activated as follows:
● Right-click Drive unit -> Target system -> Restore factory settings
● Drive unit grayed out -> "Restore factory settings" button
For more information about STARTER, see Getting Started.
Displaying toolbars
The toolbars can be activated by choosing View -> Toolbars (checkmark).
Creating and copying data sets (offline)
Drive and command data sets (DDS and CDS) can be added in the drive's configuration
screen by clicking the appropriate buttons.
For more information about data sets, see the Principles chapter for the drive system.