Basic information about the drive system
10.2 Data sets
10.2.6

Using data sets

Copying a command data set
Set parameter p0809 as follows:
1. p0809[0] = number of the command data set to be copied (source)
2. p0809[1] = number of the command data to which the data is to be copied (target)
3. p0809[2] = 1
Start copying.
Copying is finished when p0809[2] = 0.
Note
In STARTER, you can copy the command data sets (Drive -> Configuration -> "Command
data sets" tab page).
You can select the displayed command data set in the relevant STARTER screens.
Copying a drive data set
Set parameter p0819 as follows:
1. p0819[0] = Number of the drive data set to be copied (source)
2. p0819[1] = Number of the drive data set to which the data is to be copied (target)
3. p0819[2] = 1
Start copying.
Copying is finished when p0819[2] = 0.
Note
In STARTER, you can copy the drive data sets (Drive -> Configuration -> "Drive data sets"
tab page).
You can select the displayed drive data set in the relevant STARTER screens.
Copying the motor data set
Set parameter p0139 as follows:
1. p0139[0] = Number of the motor data set that is to be copied (source)
2. p0139[1] = Number of the motor data set which should be copied into (target)
3. p0139[2] = 1
Start copying.
Copying has been completed, if p0139[2] = 0.
Note
In STARTER, you can set the drive data sets via the drive configuration.