Siemens Sinamics S110 Function Manual page 49

Hide thumbs Also See for Sinamics S110:
Table of Contents

Advertisement

Copy RAM to ROM
You can use this function to save volatile Control Unit data to the non-volatile memory. This
ensures that the data is still available after the 24 V Control Unit supply has been switched
off.
This function can be activated as follows:
● Extras -> Setting -> Download -> Activate "Copy from RAM to ROM"
● Right-click Drive unit -> Target system -> Copy from RAM to ROM
● Drive unit grayed out -> "Copy from RAM to ROM" button
Download to target device
You can use this function to load the current STARTER project to the Control Unit. The data
is loaded to the working memory of the Control Unit. A reset is then triggered.
This function can be activated as follows:
● Right-click Drive unit -> Target system -> Load to target system
● Drive unit grayed out -> "Load to target system" button
● Online/offline comparison screen -> "Load to target device" button
● Project to all drive units simultaneously:
Load to PG/PC
You can use this function to load the current Control Unit project to STARTER.
This function can be activated as follows:
● Right-click Drive unit -> Target system -> Load to PG/PC
● Drive unit grayed out -> "Load project to PG/PC" button
● Online/offline comparison screen -> "Load project to PG/PC" button
Drive functions
Function Manual, 10/2008, 6SL3097-4AB10-0BP0
This means that every time data is loaded to the target system by choosing "Load project
to target system", the data is stored in the non-volatile memory.
NOTICE
The power supply to the Control Unit may first be switched off after saving has finished
(i.e. after saving has started, wait until it has finished and parameter p0977 has the
value 0 once more).
"Load project to target system" button, menu Project -> Load to target system
Commissioning with PROFIBUS
3.2 STARTER commissioning tool
49