Monitoring: telegram failure

Description
After a telegram failure and the additional monitoring time has elapsed (p2047), bit r2043.0 is
set to "1" and alarm A01920 is output. Binector output r2043.0 can be used for an
emergency stop, for example.
After a delay time has elapsed (p2044), fault F01910 is output. Fault F01910 triggers fault
response OFF3 (quick stop) for SERVO. If no OFF response is to be triggered, the fault
response can be reparameterized accordingly.
Fault F01910 can be acknowledged immediately. The drive can then be operated even
without PROFIdrive.
Figure 9-20
Note
The additional monitoring time parameter p2047 is only useful for cyclic communication.
During isochronous communication, a telegram failure should be recorded without delay, in
order to respond as quickly as possible.