SBYTCC-NEINTCLK

en/us/support/web/tsd-cisco-worldwide-contacts.html
your country.
SBYTCC-NEINTCLK
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
SDH Logical Object: EQPT
The "Standby TCC - NE Clock Is Internal Clock" condition occurs when the standby TCC NE clock switches
to the internal oscillator (clock). This alarm occurs when NE is forced to use internal clock or if all the external
clocks fails so that the NE automatically switches to internal clock. This also occurs when the sandby TCC
fails and starts using internal NE clock instead of tracking the provisioned external clock.
Clear the SBYTCC-NEINTCLK Alarm
SUMMARY STEPS
1. Clear the following alarms that relate to timing:
2. Reestablish a primary and secondary timing source according to local site practice. If none exists, refer
to the Change Node Settings chapter in the Configuration guide.
DETAILED STEPS
Step 1
Clear the following alarms that relate to timing:
FRNGSYNC , on page 207
FSTSYNC , on page 208
LOF (BITS) , on page 264
LOS (BITS) , on page 273
HLDOVRSYNC , on page 226
MANSWTOINT, on page 301
MANSWTOPRI , on page 301
MANSWTOSEC , on page 301
MANSWTOTHIRD , on page 301
SWTOPRI , on page 407
SWTOSEC , on page 408
SWTOTHIRD , on page 408
SYNC-FREQ , on page 409
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
384
to obtain a directory of toll-free Technical Support numbers for
Alarm Troubleshooting