Param-Mism - Cisco NCS 2000 series Troubleshooting Manual

Hide thumbs Also See for NCS 2000 series:
Table of Contents

Advertisement

PARAM-MISM

Step 2
If the rack installation is proper, verify that the environmental temperature of the room is not abnormally high.
Step 3
If the room temperature is not abnormally high, ensure that nothing prevents the fan-tray assembly from passing air
through the NCS system shelf.
Step 4
If airflow is not blocked, determine whether the air filter needs replacement. Refer to the
Reusable Air Filter, on page 457
Step 5
If the air filter is clean, complete the
Step 6
If the alarm fails to get cleared, complete the
When you replace a card with an identical card, you do not need to make any changes to the database.
Note
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
en/us/support/web/tsd-cisco-worldwide-contacts.html
your country.
PARAM-MISM
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
Logical Objects: AOTS, OCH, OCH-TERM, OMS, OTS
For example, this condition is raised on OPT-EDFA-17 card, when an invalid Gain setpoint is provisioned
by the control card.
The Gain setpoint for the OPT-EDFA-17 card is automatically calculated by the control card when the amplifier
is turned up. The Gain Degrade Low threshold value is always 2 dB lower than the Gain setpoint value.
The APC-OUT-OF-RANGE alarm is raised on the OPT-EDFA-17 card when the Gain setpoint value that
was calculated by the control card sets the Gain Degrade Low threshold to a value that is lower than the
minimum setpoint value. The APC-OUT-OF-RANGE alarm triggers the PARAM-MISM alarm. This is
because the Gain setpoint or the Gain Degrade Low Threshold value is outside the Gain setpoint range of the
OPT-EDFA-17 card.
PATCH-ACTIVATION-FAILED
Default Severity: Critical (CR), Non-Service-Affecting (NSA)
Logical Object: EQPT
The Patch-Activation-Failed alarm is raised when the patch fails to activate. The alarm is cleared when the
patch is disabled or when a different patch is activated. This can be verified in CTC if the patch is visible in
the active folder.
If the condition does not clear, log into the Technical Support Website at
index.html
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
350
procedure.
Remove and Reinsert (Reseat) Any Card , on page 452
Physically Replace a Card, on page 453
for more information or call Cisco TAC (1 800 553-2447).
for more information or log into
to obtain a directory of toll-free Technical Support numbers for
http://www.cisco.com/c/en/us/support/
Alarm Troubleshooting
Inspect, Clean, and Replace the
procedure.
procedure for the 100G-LC-C card.
http://www.cisco.com/c/

Advertisement

Table of Contents
loading

Table of Contents