1.2.7

Timer (T)

Function of timers (T)
When a timer is activated and the set time elapses, the timer contact with the same
number as the timer turns on.
When the timer is in the time−up state and the timer execution condition turns off, the
timer contact turns off.
TM n
Timer number
Tn
Timer contact: on
Usage restrictions
When used as contacts, there are no restrictions on the number of times that can be
used.
For the FP2/FP2SH/FP10SH, if the Initialize/Test switch is set to the upper side (the
Initialize side) in the PROG mode, the timer contact goes off. If a hold type has been
specified, it goes off as well.
Note
With the FP2SH/FP10SH, system register 4 can be set in such a way
that the timer contact is not cleared even if the Initialize/Test switch is
set to the upper side.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Time−up
Tn: on
n: Timer number
1.2
Explanation of Relays
1 - 35