Non−hold type data and hold−type data
There are two types of data registers which handle data differently when the power is
turned off or the mode is changed from RUN to PROG.:
− Hold type data registers hold their contents while operation stops and allow
operation to be restarted with the contents still effective.
− Non−hold type data registers reset when operation stops.
For the FP0 C10/C14/C16/C32, and FP−e without clock/calendar function, non−hold
type and hold type data register numbers are as shown in the following table.
Item
Data register
Non−hold type
Hold type
For theFP0 T32C/FPΣ/FP0R/FP−X/FP2/FP2SH/FP10SH, and FP−e with
clock/calendar function, system register 8 can be used to specify whether hold types
or non−hold types are to be used. If the beginning of a hold type data register is
specified using a word number, data registers before that point will be non−hold
types, and subsequent data registers will be hold types.
Value of system register 8
(initial number of hold type)
Default settings for hold types and non−hold types
Type
FPΣ, FP−X (C30, C60)
FP−X (C14)
FP−e
FP0R C10, C14, C16
FP0R C32, T32, F32
Note
For FPΣ, FP−X and FP−e, in case of not using back−up battery,
please keep the default value. Otherwise we cannot guarantee
the function of hold/non−hold value.
For the FP2/FP2SH/FP10SH, if the Initialize/Test switch is set to the upper side (the
Initialize side) in the PROG mode, all data registers (DT) are cleared to 0. Even if a hold
type has been specified, these are cleared to 0.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FP0 C10/C14/C16 and FP−e
1652 words (DT0 to DT1651)
8 words (DT1652 to DT1659)
Non-hold
type
Hold type
Non−hold type
DT0 to DT32709 (32710 words)
DT0 to DT12229 (12230 words)
DT0 to DT1651 (1652 words)
DT0 to DT11999 (12315 words)
DT0 to DT32449 (32451 words)
1.3
Explanation of Memory Areas
FP0 C32
6112 words (DT0 to DT6111)
32 words (DT6112 to DT6143)
Hold type
DT32710 to DT32765 (55 words)
DT12230 to DT12284 (55 words)
DT1652 to DT1659 (8 words)
DT12000 to DT12314 (315 words)
DT32450 to DT32764 (315 words)
1 - 45