Trouble-clearing procedures
VOLTAGELOW
....................................................................................................................................................................................................................................
Applicability
At the end of each step wait to see if the fault clears. If it does not, go to the next step.
...................................................................................................................................................................................................
Check the breakers for the alarmed shelf and verify that they are ON.
1
...................................................................................................................................................................................................
Using a DC voltmeter, measure the power going to the shelf and verify that it is within
2
the accepted limits for proper operation (-48 to -52 volts).
...................................................................................................................................................................................................
Perform a warm reset on the Equipment Controller that is raising the PWR condition.
3
CLI
WEBUI
...................................................................................................................................................................................................
Perform a cold reset on the Equipment Controller that is raising the PWR condition.
4
CLI
WEBUI
...................................................................................................................................................................................................
Reseat the Equipment Controller that is raising the PWR condition.
5
...................................................................................................................................................................................................
6
Replace the Equipment Controller that is raising the PWR condition. Follow the return
and repair process to return the card to an authorized repair center for replacement
E
N D
O F
...................................................................................................................................................................................................
VTSFDI
....................................................................................................................................................................................................................................
1830 PSS-36/PSS–32/PSS-16/PSS-4
8DG60888CAAA Release 3.6.0 and 3.6.1
Issue 1 June 2011
112SA1L, 112SCA1, 112SCX10, 112SX10L, 11DPE12E,
11DPM12, 11STAR1, 11STMM10, 11STGE12, 43SCX4,
43STA1P, 43STX4, 43STX4P, 4DPA2, 4DPA4, AHPHG, AHPLG,
ALPHG, ALPFGT, AM2017B, AM2325A, CWR, Equipment
Controller, FLC, MESH4, MT0C, MVAC, OPS, OSCT, RA2P,
SVAC, USRPNL, WR, WTOCM
config card
Select the card, click the
config card
Select the card, click the
S T E P S
card type shelf slot
reset warm
Reboot
tab, select
card type shelf slot
reset cold
tab, select
Reboot
VOLTAGELOW [Low input voltage defect]
Warm Reboot
>
Submit
>
Cold Reboot
Submit
.
.
2-351