Trouble-clearing procedures
SWEQPT
....................................................................................................................................................................................................................................
SWEQPT (Protection Switching Equipment Failure)
This condition indicates a problem on the mate card.
Severity
Service affecting?
Applicability
Corrective Action
A cold reset, reseat, or replacement of a card is service impacting if the card is currently
carrying services. To determine if any services are currently carried over a card, perform
the procedure
If there are services currently carried over the card, it may be best to wait for a
maintenance window before resetting, replacing, or reseating the card.
At the end of each step wait to see if the fault clears. If not, continue with the next step.
...................................................................................................................................................................................................
Determine if there are any hardware or software failure alarms for the transponder card
1
that is inactive and providing protection for the working one. Based on the information
presented, determine the cause of the failure and resolve that issue first using the
appropriate corrective action(s).
...................................................................................................................................................................................................
Perform a warm reset of the card of the mate transponder card.
2
CLI
WEBUI
...................................................................................................................................................................................................
Perform a cold reset of the card of the mate transponder card.
3
CLI
WEBUI
....................................................................................................................................................................................................................................
2-304
Minor
No
112SCA1, 112SCX10, 11DPE12E, 11DPM12, 11STAR,
11STMM10, 11STGE12, 43SCX4, 43STA1P, 43STX4, 43STX4P
NOTICE
Service-disruption hazard
"Reseating a Card" (p.
config card
Select the card, click the
config card
Select the card, click the
SWEQPT (Protection Switching Equipment Failure)
3-19).
card type shelf slot
reset warm
tab, select
Reboot
card_type shelf slot
reset cold
Reboot
tab, select
>
.
Warm Reboot
Submit
Cold Reboot
>
Submit
.
1830 PSS-36/PSS–32/PSS-16/PSS-4
8DG60888CAAA Release 3.6.0 and 3.6.1
Issue 1 June 2011