Alcatel-Lucent 1830 PSS-16 Maintenance And Trouble-Clearing User Manual page 529

1830 pss series photonic service switch
Table of Contents

Advertisement

Trouble-clearing procedures
RCVROPTPROG
....................................................................................................................................................................................................................................
...................................................................................................................................................................................................
Remove the fiber from the port where the LOS was raised and measure the optical power.
3
If the optical power is below the threshold level provisioned by the Photonic Manager for
the type of port, then using standard optical fiber jumper cleaning procedure, clean the
fiber, and measure the power again. If the optical power is within the required limits,
clean the receive connector on the card. If the RCVROPTPROG condition is still present
more than 10 minutes after the LOS clears, the problem may be with the card.
...................................................................................................................................................................................................
4
Perform a warm reset of the card.
CLI
WEBUI
...................................................................................................................................................................................................
5
Perform a cold reset of the card.
CLI
WEBUI
Note: Refer to Caution at the beginning of this procedure.
...................................................................................................................................................................................................
6
Reseat the card. Refer to
...................................................................................................................................................................................................
Replace the card. Refer to
7
E
N D
O F
...................................................................................................................................................................................................
RDI
RDI (Remote Defect Indication)
The OT port has detected a RDI at the MEP layer. A MEP detects RDI when it receives a
CCM frame with the RDI field set.
Severity
....................................................................................................................................................................................................................................
1830 PSS-36/PSS–32/PSS-16/PSS-4
8DG60888CAAA Release 3.6.0 and 3.6.1
Issue 1 June 2011
config card
Select the card, click the
config card
Select the card, click the
"Reseating a Card" (p.
"Replacing System Components" (p.
S T E P S
Major
RCVROPTPROG (Receiver Optimization in Progress)
card type shelf slot
reset warm
Reboot
tab, select
card_type shelf slot
Reboot
3-19).
Warm Reboot
>
Submit
reset cold
tab, select
Cold Reboot
3-20).
.
>
Submit
.
2-279

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1830 pss-321830 pss-361830 pss-4

Table of Contents