6.4.2 Anti-Resonance Control Adjustment Function Operating Procedure

6.4.2

Anti-Resonance Control Adjustment Function Operating Procedure

With this function, an operation reference is sent, and the function is executed while vibration is occurring.
Anti-resonance control adjustment function is performed from the digital operator (option) or SigmaWin+.
The function cannot be performed from the panel operator.
The following methods can be used for the anti-resonance control adjustment function.
• Using anti-resonance control for the first time
• With undetermined vibration frequency
• With determined vibration frequency
• For fine-tuning after adjusting the anti-resonance control
The following describes the operating procedure from the digital operator.
Refer to the
operations of the digital operator.
(1) Using Anti-Resonance Control for the First Time
 With Undetermined Vibration Frequency
Step
1
2
3
4
5
6-26
Σ
-V Series User's Manual, Operation of Digital Operator (No.: SIEP S800000 55) for basic key
Display after Operation
Status Display
Keys
Press the
utility function.
Use the
or
select Fn204.
Press the
Key to display the initial setting screen
for tuning mode.
Press the
"0."
Press the
played. The screen shown on the left will appear. The
detection of vibration frequencies will start and
"freq" will flash. Return to step 3 if vibration is not
detected.
Note: If vibration is not detected even when vibration
is occurring, lower the vibration detection sen-
sitivity (Pn311). When this parameter is low-
ered, the detection sensitivity will be increased.
Vibration may not be detected accurately if too
small value is set.
The vibration frequency will be displayed in "freq" if
vibration is detected.
Example of measured waveform
Operation
Key to view the main menu for the
Key to move through the list,
or
Key and set the tuning mode
Key while "Tuning Mode = 0" is dis-
Error
Error
Error
Torque reference
Torque reference
Positioning completed
Positioning completed
Positioning completed
signal
signal
signal
Ro-
ta-
tion