Sub Functions Specific To Machine Opr; Opr Retry Function - Mitsubishi Electric MELSEC iQ-F Series FX5 User Manual

Positioning control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F Series FX5:
Table of Contents

Advertisement

12.2

Sub Functions Specific to Machine OPR

The sub functions specific to machine OPR include OPR retry function and OP shift function. Each function is executed based
on the parameter setting.

OPR retry function

If a workpiece passes over the OP without stopping during the position control, the workpiece may not move back in the
direction of the OP although the machine OPR is commanded, depending on the workpiece position. In this case, the
workpiece has to be moved to a position before the near-point dog by the JOG operation or other operations to start the
machine OPR again. However, by using the OPR retry function, the machine OPR can be performed regardless of the
workpiece position.
Control details
The following shows the operation of the OPR retry function.
■OPR retry operation when the workpiece is within the range between the upper/lower limits
5.
4.
ON
Near-point dog
Zero signal
1.
The movement starts in the direction set in [Pr.44] OPR direction by Machine OPR start.
2.
The operation decelerates when Limit signal OFF is detected.
3.
After the operation has stopped due to the detection of Limit signal OFF, the operation moves at the speed set in [Pr.46]
OPR speed in the direction opposite to the direction set in [Pr.44] OPR direction.
4.
The operation decelerates when Near-point dog signal is turned off.
5.
After the operation has stopped due to turning off of Near-point dog signal, the machine OPR is performed in the
direction set in [Pr.44] OPR direction.
6.
Machine OPR is completed.
2.
1.
6.
3.
Limit signal OFF state
12 CONTROL SUB FUNCTION
12.2 Sub Functions Specific to Machine OPR
12
211