(1)
For A6CON2
This section describes the FCN-363T-T005/H specifications used by A6CON2.
Applicable wire size
AWG24
AWG26
AWG28
Special tools are required for A6CON2 wires.
Ask FUJITSU COMPONENT LIMITED about the tool use methods and adjustments.
6 WIRING
46
6.2 Connector Wiring
Wire cross-section area
Crimp height
2
0.20 to 0.24 mm
1.25 to 1.30
2
0.13 to 0.16 mm
1.20 to 1.25
2
0.088 to 0.096 mm
1.15 to 1.20
2.
Solder the wires, and cover the heat-shrinking tubing
(1).
3.
Check the terminal array, and wire to the connector. If
the connector is connected to an I/O module, it is not
necessary to connect the FG wires.
4.
Insert the connector into one side of the connector
cover, and pass the securing screws all the way
through. Then close the other side of the connector
cover.
5.
Tighten the 4 screws.
Wire cover diameter
φ1.2 or less
φ1.2 or less
φ1.2 or less
Stripped wire length
3.0 to 4.0
3.0 to 4.0
3.0 to 4.0