Mitsubishi Electric MELSEC iQ-F Series FX5 User Manual page 250

Positioning control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F Series FX5:
Table of Contents

Advertisement

Setting method
The following shows the data setting and a program example for setting the override value of the axis 1 to 200%.
■Setting data
Set the following data.
Setting item
[Cd.13]
Positioning operation
speed override
For details on the settings, refer to the following.
Page 460 [Cd.13] Positioning operation speed override
■Time Charts
The following shows the time chart of the speed change using the override function.
[Cd.184] Positioning start signal
[Cd.190] PLC READY signal
READY signal
([Md.140] Module Status: b0)
Start complete signal
([Md.31] Status: b14)
[Md.141] BUSY signal
Positioning complete signal
([Md.31] Status: b15)
Error detection signal
([Md.31] Status: b13)
■Program example
Add the following program to the control program, and write it to the CPU module.
Page 493 Override program
12 CONTROL SUB FUNCTION
248
12.5 Functions that Change Control Details
Setting
Setting detail
value
200
Set the new speed in percentage (%).
V
[Cd.13] Positioning operation
speed override
Buffer memory address
Axis 1
1513
Dwell time
200
Axis 2
1613
t