Mitsubishi Electric MELSEC iQ-F Series FX5 User Manual page 447

Positioning control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F Series FX5:
Table of Contents

Advertisement

[Md.30] External I/O signal
This area stores the on/off state of external I/O signals.
External I/O signal
OFF
ON
Values are stored in the bits corresponding to each external I/O signal. The following table shows the assignment of each
external I/O signal.
Buffer memory
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
The update cycle of this area is 0.88 ms.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Md.30] External I/O signal
If 1: Pre-analysis mode is set for [Cd.43] Analysis mode setting and [Cd.184] Positioning start signal is used
as the start trigger, the external command signal (CHG) is disabled from when the positioning data analysis
starts until a pulse input starts by inputting the start trigger. Thus, the external command signal ([Md.30]
External I/O signal: b4) is fixed to 0 during that time.
[Md.31] Status
This area stores the on/off state of various flags.
Status
OFF
ON
The following shows the flags to be stored.
Flag
In speed control flag
Speed-position switching latch
flag
Command in-position flag
b8
b7
b6
b5
b4
b3
b2
0
Axis 1
816
Description
This signal, which turns on during the speed control, is used to judge whether the operation is performed under the speed
control or position control. This signal turns off at the power-on, in the position control, and during the JOG operation or
manual pulse generator operation. During the speed-position switching control or position-speed switching control, this
signal turns on only when the speed control is performed. When the speed control is switched to the position control by the
speed-position switching signal, this signal turns off. When the position control is switched to the speed control by the
position-speed switching signal, this signal turns on.
This signal is used to interlock the movement amount change function in the speed-position switching control. During the
speed-position switching control, this signal turns on when the speed control is switched to the position control. This signal
turns off when the next positioning data is processed, and during the JOG operation or manual pulse generator operation.
This signal turns on when the remaining distance is equal to or less than the command in-position width (set by a detailed
parameter). This signal remains off with the data for which the continuous path control (P11) is specified as the operation
pattern. The state of this signal is monitored every 0.88 ms. It is not monitored under the speed control or while the speed
control is in effect during the speed-position switching control or position-speed switching control. While operations are
performed with interpolation, this signal turns on only for the starting axis. (This signal turns off for all the axes at the start.)
Stored value
0
1
Assignment of I/O signals
b0
Lower limit signal
b1
b0
b1
Upper limit signal
b2
Drive unit READY signal
b3
Stop signal
b4
External command signal
b5
Zero signal
b6
Near-point dog signal
b7
Use prohibited (fixed to 0)
b8
Deviation counter clear signal
b9 to b15
Use prohibited (fixed to 0)
Stored value
0
1
17 DATA USED FOR POSITIONING CONTROL
Axis 2
916
17.7 Monitor Data
17
445

Advertisement

Table of Contents
loading

Table of Contents