Error code
Error name
1A33H
Control method
LOOP setting error
1A34H
M code ON timing
error
1A35H
Interpolation speed
specification
method error
1A37H
Sub point setting
error
■Error at basic parameter setting range check
1A60H
Outside unit setting
range
1A61H
Outside pulse
number per rotation
range
1A62H
Outside movement
amount per rotation
range
1A63H
Outside unit
magnification range
1A64H
Pulse output mode
error
Cause and description
The number of LOOP repetition is 0 when LOOP is set in
[Da.2] Control method.
[Operation of when the error has occurred]
■At the start of operation
The operation is not performed.
■During operation
The operation stops according to the setting of [Pr.39]
Stop group 2 sudden stop selection of detailed parameter
3 (deceleration stop/sudden stop).
A value outside the setting range is set in [Da.27] M code
ON signal output timing of positioning data.
[Operation of when the error has occurred]
■At the start of operation
The operation is not performed.
■During operation
The operation stops according to the setting of [Pr.39]
Stop group 2 sudden stop selection of detailed parameter
3 (deceleration stop/sudden stop).
A value outside the setting range is set in [Da.29]
Interpolation speed specification method of the
positioning data.
[Operation of when the error has occurred]
■At the start of operation
The operation is not performed.
■During operation
The operation stops according to the setting of [Pr.39]
Stop group 2 sudden stop selection of detailed parameter
3 (deceleration stop/sudden stop).
The center point address is outside the range of -
2147483648 to 2147483647 when the circular
interpolation control has been performed with the sub
point being specified.
[Operation of when the error has occurred]
■At the start of operation
The operation is not performed.
■During operation
The operation stops immediately.
A value outside the setting range is set in [Pr.1] Unit
setting of basic parameter 1.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
A value outside the setting range is set in [Pr.2] No. of
pulses per rotation of basic parameter 1.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
A value outside the setting range is set in [Pr.3]
Movement amount per rotation of basic parameter 1.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
A value outside the setting range is set in [Pr.4] Unit
magnification of basic parameter 1.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
A value outside the setting range is set in [Pr.5] Pulse
output mode of basic parameter 1.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
Action
Set a value of 1 to 65535 as the number of LOOP
repetition. For details, refer toPage 419 [Da.10] M
code.
Set a value of 0 to 2 in [Da.27] M code ON signal output
timing. For details, refer toPage 419 [Da.27] M code
ON signal output timing.
Set a value of 0 to 2 in [Da.29] Interpolation speed
specification method. For details, refer toPage 420
[Da.29] Interpolation speed specification method.
Correct the sub point address with [Da.7] Arc address.
For details, refer toPage 416 [Da.7] Arc address.
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal. For
details, refer toPage 372 [Pr.1] Unit setting.
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal.
For details, refer to the following.
Page 373 [Pr.2] No. of pulses per rotation (16 bits)
(Ap)
Page 379 [Pr.2] No. of pulses per rotation (32 bits)
(Ap)
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal.
For details, refer to the following.
Page 374 [Pr.3] Movement amount per rotation (16
bits) (Al)
Page 380 [Pr.3] Movement amount per rotation (32
bits) (Al)
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal. For
details, refer toPage 374 [Pr.4] Unit magnification.
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal. For
details, refer toPage 375 [Pr.5] Pulse output mode.