Error code
Error name
1B11H
Setting of operation
during uncompleted
OPR
■H/W error
3001H
Fault
3002H
Internal circuit fault
3020H
CPU module error
Cause and description
A value outside the setting range is set in [Pr.58] Setting
of operation during uncompleted OPR of OPR detailed
parameter.
[Operation of when the error has occurred]
Check that READY signal ([Md.140] Module status: b0)
does not turn on.
Hardware failure
[Operation of when the error has occurred]
The operation stops immediately.
Hardware failure
[Operation of when the error has occurred]
The operation stops immediately.
An error was detected in the CPU module.
[Operation of when the error has occurred]
The operation stops slowly.
Action
Configure the value so that it is within the setting range
and then turn on [Cd.190] PLC READY signal. For
details, refer toPage 409 [Pr.58] Setting of operation
during uncompleted OPR.
Check for noise influence.
Check for noise influence.
Check the error of the CPU module and take corrective
action using the module diagnostics.
19 TROUBLESHOOTING
19.5 List of Error Codes
19
533