[Cd.6] Restart command
Set this area to restart positioning from the stop status.
• When positioning is stopped for any reason (when the axis operation status is Stopped), setting 1: Restart for this area
performs the positioning again from the stop position to the end point of the stopped positioning data.
• After the restart command is accepted, 0 is automatically stored. Storing 0 indicates the completion of the restart command
acceptance.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.6] Restart command
■Default value
The default value is 0 for all the axes.
[Cd.7] M code ON signal OFF request
Set this area to turn off M code ON signal ([Md.31] Status: b12).
• M code ON signal ([Md.31] Status: b12) is turned off by setting 1: M code ON signal is turned off for this Area.
• After the OFF request is accepted, 0 is automatically stored. Storing 0 indicates the completion of the OFF request
acceptance.
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.7] M code ON signal OFF request
■Default value
The default value is 0 for all the axes.
[Cd.8] External command valid
Set whether to validate external command signals.
External command valid
Invalidate external command
Validate external command
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.8] External command valid
■Default value
The default value is 0: Invalidate external command for all the axes.
17 DATA USED FOR POSITIONING CONTROL
458
17.8 Control Data
Axis 1
1503
Axis 1
1504
Setting value
0
1
Axis 1
1505
Axis 2
1603
Axis 2
1604
Axis 2
1605