Remove A Fan Module - Oracle Netra SPARC S7-2 Service Manual

Hide thumbs Also See for Netra SPARC S7-2:
Table of Contents

Advertisement

-> show /SYS/MB/FMx/Fy/TACH value
/SYS/MB/FM0/F0/TACH
Properties:
value = 3100.000 RPM
->
where:
x is the fan module, 0 (left fan) to 4 (right fan).
y is the fan element, 0 (primary) or 1 (secondary).
6.
If a fan module is faulty, write down which fan module is faulty, then replace it
when the new one arrives.
See
"Remove a Fan Module" on page
7.
If you are unable to determine if a fan module is faulty, seek further information.
See
"Detecting and Managing Faults" on page
Related Information
"Remove a Fan Module" on page 153
"Verify a Fan Module" on page 157
"Detecting and Managing Faults" on page 25

Remove a Fan Module

Removing a fan module is a cold-service operation. You must power off the server before you
remove the fan module.
1.
Determine which fan module to remove.
See
"Locate a Faulty Fan Module" on page
Prepare for service.
2.
See
"Preparing for Service" on page
153.
25.
152.
43.
Remove a Fan Module
Servicing Fan Modules
153

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Netra SPARC S7-2 and is the answer not in the manual?

Questions and answers

Table of Contents