Remove a Power Supply
If a power supply is faulty, you will see /SYS/PSx under the Value heading, where x is 0
■
(lower power supply) or 1 (upper power supply).
6.
Use the Oracle ILOM faultmgmt shell to identify the faulty component.
See
"Identify Faulted Components" on page
Check the Fault class and Description fields for more information.
7.
Within the Oracle ILOM interface, verify the voltage output.
-> show /SYS/PS0/V_+12V value
/SYS/PS0/V_+12V
Properties:
value = 12.031 Volts
->
8.
If a power supply is faulty, replace it.
See
"Remove a Power Supply" on page
9.
If you are unable to determine if a power supply is faulty, seek further
information.
See
"Detecting and Managing Faults" on page
Related Information
"Remove a Power Supply" on page 134
■
"Power Supply LEDs" on page 132
■
"Verify a Power Supply" on page 138
■
"Detecting and Managing Faults" on page 25
■
Remove a Power Supply
Removing a power supply is a hot-swap operation. You do not need to power off the server
before you remove the power supply.
1.
Determine which power supply to remove.
See
"Locate a Faulty Power Supply" on page
2.
Follow safety and ESD precautions.
See
"Preparing for Service" on page
134
Netra SPARC S7-2 Server Service Manual • February 2017
27.
134.
25.