Install The Top Cover - Oracle Netra SPARC S7-2 Service Manual

Hide thumbs Also See for Netra SPARC S7-2:
Table of Contents

Advertisement

Install the Top Cover

Related Information
"Secure the Drive Cage" on page 241
"Remove the Fan Tray" on page 69
"Install the Top Cover" on page 246
Install the Top Cover
Perform this task when you have previously removed the top cover.
1.
If you previously removed the PSU and air ducts, raised the drive cage, or
removed the fan tray, complete these prerequisites in this order.
See:
"Install the Air Duct" on page 236
"Install the PSU Duct" on page 240
"Secure the Drive Cage" on page 241
"Install the Fan Tray" on page 244
"Install a Fan Module" on page 155
Install all fan modules.
246
Netra SPARC S7-2 Server Service Manual • February 2017

Advertisement

Table of Contents
loading

Table of Contents