Nortel DMS-100 Series Replacement Procedures page 586

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-554 XPM card replacement procedures
NT2X90
in an RLCM-EDC RMM
5
At the RMM shelf
6
7
8
At the MAP display
9
297-8021-547 Standard 14.02 May 2001
(continued)
To busy the trunk circuits that associate with the defective card you replace,
type:
>BSY ALL
and press the Enter key.
WARNING
Static discharge may cause damage to circuit packs
Connect a wrist strap to the frame of the RMM before you
remove or insert any cards. This protects the RMM against
service degradation that static electricity causes.
Put on a wrist strap.
To replace the NT2X90 card use the common replacing a card procedure in
this document. When you complete the procedure, return to this point.
Use the information that follows to determine the next step in this procedure.
If you enter this procedure
from an alarm clearing proce-
dure
from other
To post the trunk circuits that associate with the new NT2X90 card, type:
>POST P RMM rmm_no ckt_no ckt_no
and press the Enter key.
where
rmm_no
is the number of the RMM that contains the new NT2X90 card
ckt_no
is the number of the first circuit that associates with the new card
ckt_no
is the number of the last circuit that associates with the new card
Example of a MAP response:
Do
step 18
step 9