Nortel DMS-100 Series Replacement Procedures page 362

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-330 XPM card replacement procedures
NT2X48
in an RLCM RMM
8
9
10
11
12
297-8021-547 Standard 14.02 May 2001
(end)
Installation busy the trunks that are associated with the new NT2X48 card by
typing
>BSY INB ALL
and pressing the Enter key.
Note: ESAdigitonereceiversshouldalwaysbeinanINBstatewhenthe
RLCM is under CC control, to prevent CC access. The ESA
processor will turn the circuits up to an idle state when the RLCM is in
the ESA environment.
Send any faulty cards for repair according to local procedure.
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
Go to step 12.
Obtain further assistance in replacing this card by contacting the personnel
responsible for higher level of support.
You have completed this procedure.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents