Nortel DMS-100 Series Replacement Procedures page 393

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

At the MAP display
10
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If the RTS
passed
failed
11
Send any faulty cards for repair according to local procedure.
12
Record the following items in office records:
date the card was replaced
serial number of the card
symptoms that prompted replacement of the card
13
Go to step 16.
14
Return to the Alarm Clearing Procedure that directed you to this card
replacement procedure. If necessary, go to the point where the faulty card list
was produced, identify the next faulty card on the list, and go to the
appropriate replacement procedure in this manual for that card.
15
Obtain further assistance in replacing this card by contacting personnel
responsible for higher level of support.
16
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an RSC RMM
Do
step 11
step 15
1-361
NT2X57
(end)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents