Nortel DMS-100 Series Replacement Procedures page 145

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

41
Return the RMM to service by typing
>RTS
and pressing the Enter key.
If the rmm
RTS passed
RTS failed
42
Post the ESA processor that is controlled by the alarm and control card you
have just replaced by typing
>POST ESA esa_no
and pressing the Enter key.
where
esa_no
is the number of the ESA processor to be posted, as recorded in step 5
43
Load the ESA processor by typing
>LOADPM
and pressing the Enter key.
44
Return the ESA to service by typing
>RTS
and pressing the Enter key.
If ESA processor
RTS passed
RTS failed
45
The next action depends on your reason for performing this procedure
If you were
directed to this procedure from a
maintenance procedure
not directed to this procedure
from a maintenance procedure
46
Return to the maintenance procedure that sent you to this procedure and
continue as directed.
47
For further assistance, contact the personnel responsible for the next level of
support.
48
You have completed this procedure.
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
XPM card replacement procedures
in an RLCE
Do
step 42
step 47
Do
step 45
step 47
Do
step 46
step 48
1-113
NT0X91AE
(end)