Nortel DMS-100 Series Replacement Procedures page 403

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Replacing an NT2X57 card in RSC-S RMM
At Your Current Location
1
Proceed only if you have been directed to this card replacement procedure
from a step in a maintenance procedure, are using the procedure for verifying
or accepting cards, or have been directed to this procedure by your
maintenance support group.
2
Obtain an NT2X57 replacement card. Ensure the replacement card has the
same product equipment code (PEC), including suffix, as the card that is to
be removed.
At the MAP terminal
3
Set the MAP display to PM level and post the RMM by typing
>MAPCI;MTC;PM;POST RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM where the card is to be removed
Example of a MAP display:
CM
MS
.
.
RMM
0 Quit
2 Post_
3
4
5 Trnsl
6 Tst
7 Bsy
8 RTS
9 OffL
10 LoadPM
11 Disp_
12 Next
13
14 QueryPM
15
16
17
18
4
Busy the RMM by typing
>BSY
DMS-100 Family NA100 Card Replacement Procedures Volume 4 of 7 LET0015 and up
in an RSC-S (DS-1) Model B RMM
IOD
Net
PM
.
.
.
SysB
ManB
PM
0
0
RM
0
0
RMM
5
INSV
XPM card replacement procedures
CCS
LNS
Trks
.
.
.
OffL
CBsy
0
0
0
0
1-371
NT2X57
(continued)
Ext
Appl
.
.
ISTb
InSv
0
130
0
0